LKDG series hollow filter reactorDetailed product description:Column tabs

1、 Purpose:
The LKDG filter reactor is used in low-voltage filter cabinets, connected in series with the filter capacitor, tuned to a certain resonant frequency, to absorb harmonic currents of the corresponding frequency in the power grid. There are a large number of harmonic sources such as rectifiers, converters, and frequency converters in low-voltage power grids, and the high-order harmonics generated by them can seriously endanger the safe operation of the main transformer and other electrical equipment in the system. After connecting the filter reactor in series with the capacitor, not only can it effectively absorb harmonics from the power grid, but it also improves the power factor of the system, playing a significant role in the safe operation of the system.

Environmental conditions for the use of LKDG series hollow filter reactors
1. The altitude shall not exceed 2000 meters.
2. The operating environment temperature is -25 ℃ to+45 ℃, and the relative humidity does not exceed 90%.
3. There are no harmful gases or flammable or explosive materials around.
4. The surrounding environment should have good ventilation conditions. If installed in a cabinet, ventilation equipment should be installed.

performance parameters
1. Can be used for 400V and 660V systems.
2. The rated insulation level is 3kV/min.
3. The temperature rise limit of each part of the reactor: the iron core does not exceed 85K, and the temperature rise of the coil does not exceed 95K.
4. The noise of the reactor shall not exceed 45dB.
5. The difference between the reactance values of any two phases of a three-phase reactor shall not exceed ± 3%.
6. Temperature resistance level H (180 ℃) or above.
7: Reactor quality factor 40

6、 LKDG series hollow filter reactor wiring method

LKDG series hollow filter reactor wiring diagram

Parameter table:
Filter reactors generally do not have standard specifications and are specially designed according to each filtering requirement. Taking three-phase filter reactors as an example, their typical parameters and dimensions are shown in the table below: Note: The following parameters are reference values and are not used as a basis for ordering

5 times filtering reactance:

Reactor model Inductance of reactor (μ H) Harmonic capacitor capacitance (μ F) filtering times Rated current (A) Dimensions L × W × H (mm) Installation size (mm)
LKSG-0.4-25/1986 one thousand nine hundred and eighty-six two hundred and thirty-one five twenty-five 225*155*200 175*95
LKSG-0.4-31/1582 one thousand five hundred and eighty-two two hundred and ninety five thirty-one 225*160*200 175*95
LKSG-0.4-37/1318 one thousand three hundred and eighteen three hundred and forty-six five thirty-seven 250*170*200 200*100
LKSG-0.4-50/981 nine hundred and eighty-one four hundred and sixty-two five fifty 265*190*215 215*120
LKSG-0.4-62/790 seven hundred and ninety five hundred and seventy-nine five sixty-two 280*205*230 230*125
LKSG-0.4-74/659 six hundred and fifty-nine six hundred and ninety-two five seventy-four 280*210*260 230*125
LKSG-0.4-93/527 five hundred and twenty-seven eight hundred and sixty-one five ninety-three 285*200*290 215*125
LKSG-0.4-112/438 four hundred and thirty-eight one thousand and twenty-seven five one hundred and twelve 265*200*355 215*125
LKSG-0.4-124/396 three hundred and ninety-six one thousand one hundred and thirty-seven five one hundred and twenty-four 265*205*280 215*125
LKSG-0.4-149/329 three hundred and twenty-nine one thousand three hundred and eighty-five five one hundred and forty-nine 280*220*420 230*145
LKSG-0.4-186/264 two hundred and sixty-four one thousand seven hundred and seventy five one hundred and eighty-six 330*230*420 290*145
LKSG-0.4-248/198 one hundred and ninety-eight two thousand two hundred and seventy-five five two hundred and forty-eight 325*285*480 265*175
LKSCG-0.4-310/58 one hundred and fifty-eight two thousand eight hundred and ninety-five five three hundred and ten 350*330*520 290*205
LKSG-0.4-372/132 one hundred and thirty-two three thousand five hundred and thirty-nine five three hundred and seventy-two 420*350*545 360*245

7th harmonic parameter table

Reactor model Inductance of reactor (μ H) Harmonic capacitor capacitance (μ F) filtering times Rated current (A) Dimensions L × W × H (mm) Installation size (mm)
LKSG-0.424/1009 one thousand and nine two hundred and thirty-one seven twenty-four 205*155*155 155*95
LKSG-0.4-30/810 eight hundred and ten two hundred and ninety seven thirty 205*165*155 155*95
LKSG-0.4-36/676 six hundred and seventy-six three hundred and forty-six seven thirty-six 235*165*160 185*95
LKSG-0.4-48/506 five hundred and six four hundred and sixty-two seven forty-eight 250*175*175 200*100
LKSG-0.4-61/402 four hundred and two five hundred and seventy-nine seven sixty-one 250*185*195 200*100
LKSG-0.4-73/337 three hundred and thirty-seven six hundred and ninety-two seven seventy-three 265*200*195 215*110
LKSG-0.4-91/269 two hundred and sixty-nine eight hundred and sixty-one seven ninety-one 235*158*240 185*110
LKSG-0.4-109/225 two hundred and twenty-five one thousand and twenty-seven seven one hundred and nine 235*185*260 185*110
LKSG0.4-121/191 one hundred and ninety-one one thousand one hundred and thirty-seven seven one hundred and twenty-one 238*190*280 185*110
LKSG-0.4-146/159 one hundred and fifty-nine one thousand three hundred and eighty-five seven one hundred and forty-six 250*205*315 200*125
LKSG-0.4-182/127 one hundred and twenty-seven one thousand seven hundred and seventy seven one hundred and eighty-two 250*210*340 200*125

Note: When using filter reactors for intermediate frequency furnace filtering equipment, it should be noted whether a tap of ± 5% is required (due to the special nature of intermediate frequency furnaces, which is different from other reactors), which should be raised during the inquiry. Filter reactors are mainly used in active filters, while passive filters play a role in filtering out harmonic sources,