1、 Purpose:
The LKDG filter reactor is used in low-voltage filter cabinets, connected in series with the filter capacitor, tuned to a certain resonant frequency, to absorb harmonic currents of the corresponding frequency in the power grid. There are a large number of harmonic sources such as rectifiers, converters, and frequency converters in low-voltage power grids, and the high-order harmonics generated by them can seriously endanger the safe operation of the main transformer and other electrical equipment in the system. After connecting the filter reactor in series with the capacitor, not only can it effectively absorb harmonics from the power grid, but it also improves the power factor of the system, playing a significant role in the safe operation of the system.
Environmental conditions for the use of LKDG series hollow filter reactors
1. The altitude shall not exceed 2000 meters.
2. The operating environment temperature is -25 ℃ to+45 ℃, and the relative humidity does not exceed 90%.
3. There are no harmful gases or flammable or explosive materials around.
4. The surrounding environment should have good ventilation conditions. If installed in a cabinet, ventilation equipment should be installed.
performance parameters
1. Can be used for 400V and 660V systems.
2. The rated insulation level is 3kV/min.
3. The temperature rise limit of each part of the reactor: the iron core does not exceed 85K, and the temperature rise of the coil does not exceed 95K.
4. The noise of the reactor shall not exceed 45dB.
5. The difference between the reactance values of any two phases of a three-phase reactor shall not exceed ± 3%.
6. Temperature resistance level H (180 ℃) or above.
7: Reactor quality factor 40
6、 LKDG series hollow filter reactor wiring method

Parameter table:
Filter reactors generally do not have standard specifications and are specially designed according to each filtering requirement. Taking three-phase filter reactors as an example, their typical parameters and dimensions are shown in the table below: Note: The following parameters are reference values and are not used as a basis for ordering
5 times filtering reactance:
| Reactor model |
Inductance of reactor (μ H) |
Harmonic capacitor capacitance (μ F) |
filtering times |
Rated current (A) |
Dimensions L × W × H (mm) |
Installation size (mm) |
| LKSG-0.4-25/1986 |
one thousand nine hundred and eighty-six |
two hundred and thirty-one |
five |
twenty-five |
225*155*200 |
175*95 |
| LKSG-0.4-31/1582 |
one thousand five hundred and eighty-two |
two hundred and ninety |
five |
thirty-one |
225*160*200 |
175*95 |
| LKSG-0.4-37/1318 |
one thousand three hundred and eighteen |
three hundred and forty-six |
five |
thirty-seven |
250*170*200 |
200*100 |
| LKSG-0.4-50/981 |
nine hundred and eighty-one |
four hundred and sixty-two |
five |
fifty |
265*190*215 |
215*120 |
| LKSG-0.4-62/790 |
seven hundred and ninety |
five hundred and seventy-nine |
five |
sixty-two |
280*205*230 |
230*125 |
| LKSG-0.4-74/659 |
six hundred and fifty-nine |
six hundred and ninety-two |
five |
seventy-four |
280*210*260 |
230*125 |
| LKSG-0.4-93/527 |
five hundred and twenty-seven |
eight hundred and sixty-one |
five |
ninety-three |
285*200*290 |
215*125 |
| LKSG-0.4-112/438 |
four hundred and thirty-eight |
one thousand and twenty-seven |
five |
one hundred and twelve |
265*200*355 |
215*125 |
| LKSG-0.4-124/396 |
three hundred and ninety-six |
one thousand one hundred and thirty-seven |
five |
one hundred and twenty-four |
265*205*280 |
215*125 |
| LKSG-0.4-149/329 |
three hundred and twenty-nine |
one thousand three hundred and eighty-five |
five |
one hundred and forty-nine |
280*220*420 |
230*145 |
| LKSG-0.4-186/264 |
two hundred and sixty-four |
one thousand seven hundred and seventy |
five |
one hundred and eighty-six |
330*230*420 |
290*145 |
| LKSG-0.4-248/198 |
one hundred and ninety-eight |
two thousand two hundred and seventy-five |
five |
two hundred and forty-eight |
325*285*480 |
265*175 |
| LKSCG-0.4-310/58 |
one hundred and fifty-eight |
two thousand eight hundred and ninety-five |
five |
three hundred and ten |
350*330*520 |
290*205 |
| LKSG-0.4-372/132 |
one hundred and thirty-two |
three thousand five hundred and thirty-nine |
five |
three hundred and seventy-two |
420*350*545 |
360*245 |
7th harmonic parameter table
| Reactor model |
Inductance of reactor (μ H) |
Harmonic capacitor capacitance (μ F) |
filtering times |
Rated current (A) |
Dimensions L × W × H (mm) |
Installation size (mm) |
| LKSG-0.424/1009 |
one thousand and nine |
two hundred and thirty-one |
seven |
twenty-four |
205*155*155 |
155*95 |
| LKSG-0.4-30/810 |
eight hundred and ten |
two hundred and ninety |
seven |
thirty |
205*165*155 |
155*95 |
| LKSG-0.4-36/676 |
six hundred and seventy-six |
three hundred and forty-six |
seven |
thirty-six |
235*165*160 |
185*95 |
| LKSG-0.4-48/506 |
five hundred and six |
four hundred and sixty-two |
seven |
forty-eight |
250*175*175 |
200*100 |
| LKSG-0.4-61/402 |
four hundred and two |
five hundred and seventy-nine |
seven |
sixty-one |
250*185*195 |
200*100 |
| LKSG-0.4-73/337 |
three hundred and thirty-seven |
six hundred and ninety-two |
seven |
seventy-three |
265*200*195 |
215*110 |
| LKSG-0.4-91/269 |
two hundred and sixty-nine |
eight hundred and sixty-one |
seven |
ninety-one |
235*158*240 |
185*110 |
| LKSG-0.4-109/225 |
two hundred and twenty-five |
one thousand and twenty-seven |
seven |
one hundred and nine |
235*185*260 |
185*110 |
| LKSG0.4-121/191 |
one hundred and ninety-one |
one thousand one hundred and thirty-seven |
seven |
one hundred and twenty-one |
238*190*280 |
185*110 |
| LKSG-0.4-146/159 |
one hundred and fifty-nine |
one thousand three hundred and eighty-five |
seven |
one hundred and forty-six |
250*205*315 |
200*125 |
| LKSG-0.4-182/127 |
one hundred and twenty-seven |
one thousand seven hundred and seventy |
seven |
one hundred and eighty-two |
250*210*340 |
200*125 |
Note: When using filter reactors for intermediate frequency furnace filtering equipment, it should be noted whether a tap of ± 5% is required (due to the special nature of intermediate frequency furnaces, which is different from other reactors), which should be raised during the inquiry. Filter reactors are mainly used in active filters, while passive filters play a role in filtering out harmonic sources,