HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerOutdoor vacuum circuit breaker → ZW32B-12 series column type outdoor high-voltage vacuum circuit breaker
Column tabs 
Product name: ZW32B-12 series column type outdoor high-voltage vacuum circuit breaker
specification: ZW32B-12 series column type outdoor high-voltage vacuum circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


ZW32B-12 series column type outdoor high-voltage vacuum circuit breakerDetailed product description:Column tabs
ZW32B-12 series column outdoor high-voltage vacuum circuit breaker is an outdoor high-voltage switchgear with three-phase AC 50Hz and rated voltage of 12KV. Suitable for breaking and closing load current, overload current, and short-circuit current of urban or rural distribution systems.
The circuit breaker is a brand new compact design. Fully enclosed structure, unique arc extinguishing chamber packaging technology, good sealing performance, moisture-proof, anti condensation, suitable for high temperature and humid areas. The ZW32B-12G circuit breaker isolation switch combination is composed of two main parts: ZW32B circuit breaker isolation switch.

Main technical parameters of ZW32B-12 series column outdoor high-voltage vacuum circuit breaker

serial number
parameter name
unit
ZW32B-12
/T400-12.5
ZW32B-12
/T630-16
ZW32B-12
/T630-20
one
rated voltage
KV
twelve
two
rated current
A
four hundred
six hundred and thirty
six hundred and thirty
three
Rated short-circuit breaking current
KA
twelve point five
sixteen
twenty
four
Rated short-circuit closing current (peak)
thirty-one point five
forty
fifty
five
Rated peak withstand current
thirty-one point five
forty
fifty
six
Rated short-time withstand current
twelve point five
sixteen
twenty
seven
Rated short-circuit duration
S
four
eight
Rated Absolute
Edge level
1-minute power frequency withstand voltage
KV
Interphase, ground 42, fracture 48
Lightning impulse withstand voltage (peak value)
Interphase, ground 72, fracture 75
nine
Rated operating sequence
Fen-0.3S-180S-Fen (electric mechanism)
ten
Rated short-circuit current breaking times
time
thirty
eleven
mechanical life
ten thousand
twelve
Rated operating voltage (switching coil)
A/DC220、110、DC24
thirteen
Allowable cumulative thickness of wear for dynamic and static contacts
V
three
fourteen
Rated current of overcurrent release device
mm
five
fifteen
Current ratio of current transformer
A
200/5, 400/5, 600/5
sixteen
Contact opening distance
mm

9±1

seventeen
Contact overtravel

2±0.5

eighteen
Average opening speed
m/s

1.2±0.3

nineteen
Average closing speed

0.6±0.2

twenty
Opening time
ms

20~40

twenty-one
closing time

30~60

twenty-two
Closing bounce time

≤2

twenty-three
Synchronization of three-phase opening and closing
twenty-four
DC resistance of each phase circuit
μΩ
≤80
twenty-five

energy storage motor
rated voltage
V
DC/220、110、24
rated power
W
forty
Energy storage time
S
≤8
twenty-six
quality
kg
eighty-five


ZW32B-12 series column outdoor high-voltage vacuum circuit breaker, external installation dimensions

ZW32B-12 Series Column Outdoor High Voltage Vacuum Circuit Breaker Installation Dimensional Drawing

Note: The current transformer ratio can be selected according to customer requirements

ZW32B-12 series column type outdoor high-voltage vacuum circuit breaker
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference