| Product name: | ZN73A-12/D Indoor High Voltage Permanent Magnet Vacuum Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||

|
project |
unit |
parameter |
|
rated voltage |
KV |
twelve |
|
Rated short-time power frequency withstand voltage (1min) |
KV |
forty-two |
|
Rated lightning impulse high voltage (peak) |
KV |
seventy-five |
|
rated frequency |
HZ |
fifty |
|
rated current |
A |
630-1250 1250-3150 1250-4000 |
|
Rated short-circuit breaking current |
kA |
20 25 31.5 40 |
|
Rated thermal stability current (effective value) |
kA |
20 25 31.5 40 |
|
Rated peak withstand current |
kA |
50 63 80 100 |
|
Rated short-circuit closing current |
kA |
50 63 80 100 |
|
Rated short-circuit duration |
S |
four |
|
Secondary circuit power frequency withstand voltage (1min) |
V |
two thousand |
|
Rated operating sequence |
Off/off -0.3s - on/off -180s - on/off/off/on/off | |
|
Rated breaking current of single/back-to-back capacitor bank |
A |
six million three hundred and eight thousand and four hundred |
|
Opening time (rated voltage) |
ms |
≤50 |
|
Closing time (rated voltage) |
ms |
≤75 |
|
mechanical life |
time |
≥100000 |
|
Rated short-circuit current breaking times |
mm |
thirty |
|
Allowable cumulative thickness of wear for dynamic and static contacts |
mm |
three |
|
Contact opening distance |
mm |
11±1* |
|
overstroke |
mm |
3.5±0.5 |
|
Contact closing bounce time |
ms |
≤2(40KA≤3) |
|
Three phase asynchronous opening and closing |
ms |
≤2 |
|
Average opening speed |
m/s |
0.8-1.2 |
|
Average closing speed |
m/s |
0.5-0.8 |
|
Interphase center distance |
mm |
210 275 |
|
Main electrical circuit resistance |
uΩ |
≤45(Less than 1250A)≤40(1600-2000A)≤30(more than 2500A) |
|
Contact closing contact pressure |
N |
2000±200(20kA) 2400±200(25KA) 3100±200(31.5KA) 4300±200(40KA) |
There are special requirements for the operation power supply (such as DC110V, AC/DC operation), and the technical parameters of the permanent magnet mechanism need to be adjusted.
The contact distance of Westinghouse arc extinguishing chamber is 9 ± 1mm
The contact opening distance of Siemens arc extinguishing chamber is 8 ± 1mm
Appearance and installation dimensions of ZN73A-12/D indoor high-voltage permanent magnet vacuum circuit breaker

ZN73A-12/D indoor high-voltage permanent magnet vacuum circuit breaker