HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerOutdoor vacuum circuit breaker → ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group
Column tabs 
Product name: ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group
specification: ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker groupDetailed product description:Column tabs
The ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group mainly consists of two ZW8 outdoor vacuum circuit breakers and a dual power automatic conversion controller. It is suitable for dual power supply systems with AC 50Hz, rated voltage 12kV and below, mainly powered by the main power supply. When the main power fails, it automatically switches to the backup power supply, and when the main power comes in, it automatically switches to the main power supply. This set of equipment is mainly used in important situations where power outages are allowed.

ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group model and its meaning:
ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group model description
Usage environment:
1. Altitude: not exceeding 1000 meters (for high source type).
2. Surrounding air temperature: -45 ℃ to+40 ℃.
3. Relative temperature: daily average not exceeding 95%, monthly average not exceeding 90%.
4. Wind speed: not exceeding 35m/s.
5. No flammable, explosive, chemical corrosion, or severe vibration hazards.  

ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group main technical parameters:

Project
unit
quantity
rated voltage
KV
twelve
Rated insulation level
1min power frequency withstand voltage
Dry test
KV
forty-two
Wet test (ground test)
thirty-four
Lightning impulse withstand voltage (peak value)
seventy-five
rated current
A
six hundred and thirty
rated frequency
Hz
fifty
Rated short-circuit breaking current
KA
16. 20
Rated short-circuit closing current (peak)
40, 50
Rated peak withstand current
40, 50
Rated short-circuit withstand current 4s
16. 20
operating sequence
Min-0.3s HeFen-180s HeFen
Rated short-circuit current breaking times
time
thirty
mechanical life
time
ten thousand
Secondary circuit 1min power frequency withstand voltage
kV
three
Rated current of overcurrent release device
A
five


The external dimensions and installation dimensions of ZW8Q-12 series outdoor single circuit breaker:

ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker assembly installation dimension diagram

ZW8Q-12 series outdoor dual power switching controller external dimensions and installation dimensions:

ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker assembly external dimension drawing


Ordering Notice:
1. Product model, name, quantity, rated breaking current, and whether an isolation switch is included. Changes in current transformers, quantity, auxiliary power supply mode, and voltage levels for manual, electric, and electric operation of the operating mechanism.
2. Technical requirements and functional configuration of dual power automatic switching circuit breakers.
3. Delivery location and transportation method.
If users have special requirements, please consult with us to resolve them.   

ZW8Q-12 series outdoor dual power automatic conversion vacuum circuit breaker group
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference