| Product name: | ZN33B-12 Suspended High Voltage Vacuum Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
| serial number S.N |
project Item |
unit Unit |
numerical value Digital Value | |
| one | rated voltage Rated Voltage |
kV | twelve | |
| two | Rated short-time power frequency withstand voltage (1min) Rated Short Period Work Frequency Voltage Endurance (1 min) |
forty-two | ||
| three | Rated lightning impulse withstand voltage (peak) Rated Thunder and Lightening Striking Endurance Voltage (Peak Value) |
seventy-five | ||
| four | rated frequency Rated Frequency |
HZ | fifty | |
| five | rated current Rated Current |
A | 630 1250 | 630 1250 |
| six | Rated short-circuit breaking current Rated Short-circuit On and Off Current |
KA | twenty | thirty-one point five |
| seven | Rated short-time withstand current Rated Short Period Endurance Current |
twenty | thirty-one point five | |
| eight | Rated short-circuit duration Rated Short-circuit Continuing Time |
S | four | |
| nine | Rated peak withstand current Rated Peak Value Endurance Current |
kA | fifty | eighty |
| ten | Rated short-circuit closing current Rated Short-circuit On-switch Current |
fifty | eighty | |
| eleven | Secondary circuit power frequency withstand voltage (1min) Secondary Loop Work Frequency Voltage Endurance (1 minute) |
V | two thousand | |
| twelve |
Rated Single/Back to Back Capacitor Group On and Off Current |
A | 630/400 | |
| thirteen | Rated capacitor bank closing inrush current Rated Capacitor Group Enclosed Surge |
KA | 12.5 (Frequency not larger than 1000Hz) | |
| fourteen | mechanical life Mechanical Lifespan |
time Times |
twenty thousand | |
| fifteen | Rated current breaking times Rated Current On and Off Times |
twenty thousand | ||
| sixteen | Rated short-circuit current breaking times Rated Short-circuit Current On and Off Times |
fifty | ||
| seventeen | Allowable cumulative thickness of wear for dynamic and static contacts Allowed Worm Accumulated Thickness of Dynamite and Static Contact Head |
mm | three | |
| eighteen | Rated operating sequence Rated Operating Sequence |
OFF minute -0.3S-ON/OFF combined minute -180S-ON/OFF | ||