| project |
unit |
data |
| Rated voltage Ur |
kV |
twelve |
| Rated insulation level |
1-minute power frequency withstand voltage Ud (effective value) |
kV |
Fracture, phase to phase, ground to ground |
forty-two |
| Lightning impulse withstand voltage Up (peak) |
kV |
Fracture, phase to phase, ground to ground |
seventy-five |
| Rated frequency fr |
Hz |
fifty |
| Rated current Ir |
A |
630, 1250, 1600, 2000, 2500, 3150, 4000 |
| Rated short-circuit breaking current Isc (effective value) |
kA |
25, 31.5, 40, 50 |
| Rated peak withstand current Ip |
kA |
63, 80, 100, 125 |
| Rated short-circuit closing current |
kA |
63, 80, 100, 125 |
| Rated short-time withstand current Ik (effective value) |
kA |
25, 31.5, 40, 50 |
| Rated short-circuit duration tk |
s |
four |
| Rated back-to-back capacitor bank breaking current Ibb (effective value) |
A |
four hundred |
| Rated back-to-back capacitor bank closing inrush current Ibi (peak) |
kA |
20 (frequency 4250Hz) |
| Rated cable charging breaking current Ic (effective value) |
A |
twenty-five |
| Rated operating sequence |
Automatic reclosing: O-0.3s-CO-180-CO |
| Non automatic reclosing: O-180s-CO-180-CO |
| Rated power supply voltage Uop for closing and opening devices |
V |
AC:110, 220; DC:110, 220 |
| Rated power supply voltage Ua of auxiliary circuit |
V |
AC:110, 220; DC:110, 220 |
| Mechanical lifespan* |
210mm phase to phase distance circuit breaker |
time |
twenty thousand |
| Circuit breakers with phase spacing of 150mm and 275mm |
ten thousand |
| Classification: Mechanical life/Electrical life/Capacitive current breaking |
M2/E2/C2 |