HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerIndoor vacuum circuit breaker → Indoor high-voltage vacuum circuit breaker
Column tabs 
Product name: Indoor high-voltage vacuum circuit breaker
specification: Indoor high-voltage vacuum circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Indoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


Indoor high-voltage vacuum circuit breakerDetailed product description:Column tabs
Overview:
The VS1-12 series indoor high-voltage vacuum circuit breaker is mainly used in 12kV power systems as a protection and control unit for power equipment in power plants, substations, and industrial and mining enterprises. Suitable for frequent operating places.

Key Features:
1. The circuit breaker arranges the arc extinguishing chamber and the spring operating mechanism as a unified whole. This structural design makes the operating performance of the operating mechanism more in line with the required performance of the arc extinguishing chamber opening and closing, reduces unnecessary intermediate links, lowers energy consumption and noise, and greatly improves the operating performance of the circuit breaker.
2. The arc extinguishing chamber is a ceramic insulated shell with a large creepage distance, using copper chromium contacts, cup-shaped longitudinal magnetic structure, and large breaking capacity.
3. The primary conductive circuit of the circuit breaker is installed inside an insulation cylinder made of epoxy resin cast using APG technology, effectively preventing external factors such as external impact and polluted environment from affecting the arc extinguishing chamber.
4. The maximum rated current reaches 5000A, and the rated short-circuit breaking current reaches 50kA, which are the highest parameters in China.

Main technical parameters of VS1-12/5000-50 indoor high-voltage vacuum circuit breaker:

serial number

project

unit

Numerical value

one

rated voltage

kV

twelve

two

Power frequency withstand voltage (1min)

forty-two

three

Lightning impulse withstand voltage (peak value)

seventy-five

four

rated frequency

Hz

fifty

five

rated current

A

630, 1250, 1600, 2000, 2500, 3150, 4000, 5000

six

Rated short-circuit breaking current (effective value)

kA

twenty

twenty-five

thirty-one point five

forty

fifty

seven

Rated short-time withstand current (effective value)

twenty

twenty-five

thirty-one point five

forty

fifty

eight

Rated short-circuit current duration

S

four

nine

Rated peak withstand current (peak)

kA

fifty

sixty-three

eighty

one hundred

one hundred and twenty-five

ten

Rated short-circuit closing current (peak)

fifty

sixty-three

eighty

one hundred

one hundred and twenty-five

eleven

Rated breaking current of single/back-to-back capacitor bank

A

630/400

twelve

mechanical life

time

twenty thousand

thirteen

Rated short-circuit current breaking times

thirty

twenty

fourteen

Rated operating sequence

★ Min-0.3 s - HeFen-180 s - HeFen ☆ Min-180s - HeFen-180 s - HeFen


Forced air cooling is required for temperatures above 4000A
Ordering Instructions:
1. Name, model, specifications, quantity, and delivery time of the circuit breaker;
2. Select the control circuit schematic and rated operating voltage;
3. Configuration scheme for overcurrent protection and closing locking components;
4. Names and quantities of spare parts and components;
5. If the user has any other requirements, they can specify them when placing an order.

Indoor high-voltage vacuum circuit breaker
Product Category