ZW30-40.5 series outdoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz high-voltage switchgear mainly used for control and protection of 40.5KV power transmission and transformation systems. It can also be used for normal operation and short-circuit protection of multiple power grids and industrial and mining enterprises, and can be used as a connecting circuit breaker and for opening and closing capacitor groups.
ZW30-40.5 outdoor high-voltage vacuum circuit breaker is equipped with CT17-IVB spring energy storage operating mechanism, which can remotely control electric energy storage, electric opening and closing operations, as well as on-site manual energy storage, manual opening and closing operations.
Advantages:
Three column structure, small footprint, small volume, and light weight;
It can carry 6 outdoor current transformers, and the measurement accuracy of the transformers can reach 0.2 and 0.2S levels, and the protection accuracy can be 5P and 10P levels;
Can avoid the trouble of disassembling the circuit breaker when the current transformer fails;
The creepage distance of porcelain bottles is 3.1 cm/kV, suitable for any area with an altitude of 3000 meters (Class II polluted area) or 1000 meters (Class IV polluted area) and below.
Mechanical characteristic parameters of ZW30-40.5 outdoor high-voltage vacuum circuit breaker:
| serial number |
name |
unit |
data |
| one |
Contact switch |
mm |
20±2 |
| two |
overstroke |
4±1 |
| three |
Allowable wear thickness of contacts |
three |
| four |
Average opening speed (0-12mm before contact buffer) |
m/s |
1.85-2.15 |
Measure at the pivot of the base |
| five |
Average closing speed (full stroke 20mm) |
0.7-1.0 |
| six |
Contact closing bounce time |
ms |
≤3 |
| seven |
Three phase asynchronous disconnection |
≤2 |
| eight |
Three phase closing asynchrony |
≤2 |
| nine |
closing time |
45-100 |
| ten |
Opening time |
35-65 |
| eleven |
Resistance of each conductive circuit |
μΩ |
≤40 |
| twelve |
Interphase center distance |
mm |
750±3 |
Product Technical Parameters:
| parameter item |
Product model |
|
ZW30-40.5 |
| Rated voltage (kV) |
forty point five |
| Rated current (A) |
two thousand |
| Rated insulation level (kV) |
Lightning impulse withstand voltage |
one hundred and eighty-five |
| power frequency withstand voltage |
ninety-five |
| Rated short-time withstand current/rated short-circuit breaking current (kA) |
25 31.5 |
| Rated peak withstand current/rated short-circuit closing current (kA) |
eighty |
| Open and close the current of a single capacitor bank (A) |
six hundred and thirty |
| Rated out of step breaking current (kA) |
eight |
| Rated operating sequence |
Min-0.3s HeFen-180s HeFen |
| Accumulated breaking times under rated short-circuit breaking current (times) |
twenty |
| Mechanical lifespan (times) |
ten thousand |
| Rated short-circuit duration (s) |
four |
| Leakage rate%/year |
≤1 |
| Rated pressure of sulfur hexafluoride gas (pressure gauge at 20 ℃) |
0.02 MPa |
| Weight (kg) |
Circuit breaker body |
seven hundred and fifty |
| Sulfur hexafluoride gas |
zero point zero eight |
ZW30-40.5 Outdoor High Voltage Vacuum Circuit Breaker