HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerOutdoor vacuum circuit breaker → ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker
Column tabs 
Product name: ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker
specification: ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Outdoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: Shanghai
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


ZW39-40.5 series outdoor high-voltage AC vacuum circuit breakerDetailed product description:Column tabs

ZW39-40.5 outdoor high-voltage AC vacuum circuit breaker is suitable for use in AC 40.5kV, 50Hz three-phase power systems for control and protection in industrial and mining enterprises, power plants, and substations. This product can be operated frequently and can also be used as a contact circuit breaker.
Main characteristics of circuit breakers
ZW39-40.5W/T2000-31.5 outdoor vacuum circuit breaker solves the major problem of internal condensation and moisture absorption caused by temperature and humidity changes in similar domestic products, which leads to a decrease in insulation strength, as well as the problem of aging due to exposed insulation rods. It strengthens the insulation strength of the inner surface of the sleeve and insulation components. In addition, the circuit breaker also has the following characteristics:
The preferred contact material for the vacuum arc extinguishing chamber ensures that the average small current interruption value is below 4A, effectively suppressing operational overvoltage.
The circuit breaker has strong breaking capacity, with a breaking short-circuit current of 31.5kA for 30 times.
Adopting the CT10A improved mechanism with reliable performance, it can operate frequently and has a lifespan of up to 10000 times.
This product can adapt to environmental requirements at an altitude of 3000 meters and has a high level of external insulation.
Circuit breakers can be equipped with internal or external transformers:
Each phase of the circuit breaker can be equipped with 4 internal current transformers. The iron core of the internal current transformer is made of microcrystalline alloy and high magnetic conductivity material. The accuracy of current transformers with 200A and above can reach 0.2 level and 0.2S level. The overall structure of the circuit breaker is compact, and the wrapping process of the secondary winding of the transformer has been fully optimized. Fully ensure that the shape of the transformer coil after wrapping is regular, without burrs, and does not loosen during drying. After being installed in the host, there is no deformation, and the electric field is uniform.
This product is filled with slightly positive pressure SF6 gas (without internal CT: 0.02MPa, internal CT: 0.2MPa) in the vacuum arc extinguishing chamber and porcelain sleeve, ensuring that condensation and moisture absorption will not occur inside. At the same time, it can avoid defects such as bubbles, penetrating discharge, and difficulty in maintenance and repair caused by filling organic insulation materials inside the original ZW7 series products.
The main secondary electrical components are selected from high-quality products with high operational reliability.
The surface treatment of exposed parts of the product is hot-dip galvanized or directly made of high-quality stainless steel sheet, with superior corrosion resistance.
This product can directly replace the SW2-35 type low oil circuit breaker (with the same installation size), and with a transition bracket, it can replace various types of multi oil circuit breakers, making it an ideal oil-free circuit breaker.

3 Main Technical Parameters

Preface
number
Project Unit Parameters
one rated voltage kV forty point five
two 1-minute power frequency withstand voltage
(Fracture/phase to phase, to ground)
(95+23)/95 * (dry test)
85 * (wet test)
three Rated lightning impulse withstand voltage (peak) (fracture/phase to phase, to ground) (185+30)/185*
four rated current A two thousand
five Rated short-circuit breaking current kA thirty-one point five
six Rated short-time withstand current thirty-one point five
seven Rated short-circuit closing current (peak) eighty
eight Rated peak withstand current eighty
nine Rated out of step breaking current eight
ten Grounding fault breaking current of different phases twenty-seven point four
eleven Rated short-circuit duration

S

four
twelve Rated short-circuit breaking current breaking times time thirty
thirteen Rated breaking current of a single capacitor bank A six hundred and thirty
fourteen Rated operating sequence O-0.3s-CO-180s-CO
fifteen mechanical life time ten thousand
seventeen Vacuum interrupter
Vacuum degree of (TD-40.5/2000-31.5W)
Newly manufactured arc extinguishing chamber Pa <1.33×10-3
Within the 20-year storage period Pa <6.6×10-2
eighteen Weight of circuit breaker

kg

750 (no CT, attached CT)
1000 (with CT)
nineteen Rated inflation pressure (20 ℃) MPa 0.02 (no CT, external CT)/0.2 (internal CT)
twenty SF6 gas replenishment alarm pressure (20 ℃) MPa 0.15 (with attached CT)
twenty-one Moisture content of SF6 gas ≤ 250 × 10-6 (CT included)
twenty-two External insulation creepage distance fracture mm ≥1255
to the ground ≥1255

Note: The * value represents the external insulation level of the product, which is adjusted according to an altitude of 3000m during testing. The three values are 122kV, 109 kV, and 237 kV, respectively.

4. Ordering Notice
Circuit breaker model and specifications;
Rated electrical parameters (voltage, current, breaking current, etc.);
Operating voltage of the operating mechanism and motor voltage;
The quantity, current ratio, level combination, secondary load, and installation location of the attached current transformers;
Names and quantities of spare parts, specialized tools, and equipment (to be ordered separately).
5. Outline and installation dimension diagram

ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker installation dimension diagram 1

ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker installation dimension diagram 2
ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker

ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker
Product Category