| Product name: | ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Outdoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
ZW39-40.5 outdoor high-voltage AC vacuum circuit breaker is suitable for use in AC 40.5kV, 50Hz three-phase power systems for control and protection in industrial and mining enterprises, power plants, and substations. This product can be operated frequently and can also be used as a contact circuit breaker.
Main characteristics of circuit breakers
ZW39-40.5W/T2000-31.5 outdoor vacuum circuit breaker solves the major problem of internal condensation and moisture absorption caused by temperature and humidity changes in similar domestic products, which leads to a decrease in insulation strength, as well as the problem of aging due to exposed insulation rods. It strengthens the insulation strength of the inner surface of the sleeve and insulation components. In addition, the circuit breaker also has the following characteristics:
The preferred contact material for the vacuum arc extinguishing chamber ensures that the average small current interruption value is below 4A, effectively suppressing operational overvoltage.
The circuit breaker has strong breaking capacity, with a breaking short-circuit current of 31.5kA for 30 times.
Adopting the CT10A improved mechanism with reliable performance, it can operate frequently and has a lifespan of up to 10000 times.
This product can adapt to environmental requirements at an altitude of 3000 meters and has a high level of external insulation.
Circuit breakers can be equipped with internal or external transformers:
Each phase of the circuit breaker can be equipped with 4 internal current transformers. The iron core of the internal current transformer is made of microcrystalline alloy and high magnetic conductivity material. The accuracy of current transformers with 200A and above can reach 0.2 level and 0.2S level. The overall structure of the circuit breaker is compact, and the wrapping process of the secondary winding of the transformer has been fully optimized. Fully ensure that the shape of the transformer coil after wrapping is regular, without burrs, and does not loosen during drying. After being installed in the host, there is no deformation, and the electric field is uniform.
This product is filled with slightly positive pressure SF6 gas (without internal CT: 0.02MPa, internal CT: 0.2MPa) in the vacuum arc extinguishing chamber and porcelain sleeve, ensuring that condensation and moisture absorption will not occur inside. At the same time, it can avoid defects such as bubbles, penetrating discharge, and difficulty in maintenance and repair caused by filling organic insulation materials inside the original ZW7 series products.
The main secondary electrical components are selected from high-quality products with high operational reliability.
The surface treatment of exposed parts of the product is hot-dip galvanized or directly made of high-quality stainless steel sheet, with superior corrosion resistance.
This product can directly replace the SW2-35 type low oil circuit breaker (with the same installation size), and with a transition bracket, it can replace various types of multi oil circuit breakers, making it an ideal oil-free circuit breaker.
3 Main Technical Parameters
| Preface number |
Project | Unit | Parameters | ||
| one | rated voltage | kV | forty point five | ||
| two | 1-minute power frequency withstand voltage (Fracture/phase to phase, to ground) |
(95+23)/95 * (dry test) | |||
| 85 * (wet test) | |||||
| three | Rated lightning impulse withstand voltage (peak) (fracture/phase to phase, to ground) | (185+30)/185* | |||
| four | rated current | A | two thousand | ||
| five | Rated short-circuit breaking current | kA | thirty-one point five | ||
| six | Rated short-time withstand current | thirty-one point five | |||
| seven | Rated short-circuit closing current (peak) | eighty | |||
| eight | Rated peak withstand current | eighty | |||
| nine | Rated out of step breaking current | eight | |||
| ten | Grounding fault breaking current of different phases | twenty-seven point four | |||
| eleven | Rated short-circuit duration |
S |
four | ||
| twelve | Rated short-circuit breaking current breaking times | time | thirty | ||
| thirteen | Rated breaking current of a single capacitor bank | A | six hundred and thirty | ||
| fourteen | Rated operating sequence | O-0.3s-CO-180s-CO | |||
| fifteen | mechanical life | time | ten thousand | ||
| seventeen | Vacuum interrupter Vacuum degree of (TD-40.5/2000-31.5W) |
Newly manufactured arc extinguishing chamber | Pa | <1.33×10-3 | |
| Within the 20-year storage period | Pa | <6.6×10-2 | |||
| eighteen | Weight of circuit breaker |
kg |
750 (no CT, attached CT) 1000 (with CT) | ||
| nineteen | Rated inflation pressure (20 ℃) | MPa | 0.02 (no CT, external CT)/0.2 (internal CT) | ||
| twenty | SF6 gas replenishment alarm pressure (20 ℃) | MPa | 0.15 (with attached CT) | ||
| twenty-one | Moisture content of SF6 gas | ≤ 250 × 10-6 (CT included) | |||
| twenty-two | External insulation creepage distance | fracture | mm | ≥1255 | |
| to the ground | ≥1255 | ||||
Note: The * value represents the external insulation level of the product, which is adjusted according to an altitude of 3000m during testing. The three values are 122kV, 109 kV, and 237 kV, respectively.
4. Ordering Notice
Circuit breaker model and specifications;
Rated electrical parameters (voltage, current, breaking current, etc.);
Operating voltage of the operating mechanism and motor voltage;
The quantity, current ratio, level combination, secondary load, and installation location of the attached current transformers;
Names and quantities of spare parts, specialized tools, and equipment (to be ordered separately).
5. Outline and installation dimension diagram


ZW39-40.5 series outdoor high-voltage AC vacuum circuit breaker