HomeYour location:HomeHigh voltage electrical applianceshigh-voltage circuit breakerIndoor vacuum circuit breaker → CVS Sealed pole vacuum circuit breaker
Column tabs 
Product name: CVS Sealed pole vacuum circuit breaker
specification: CVS Sealed pole vacuum circuit breaker
  Zoom Zoom in on the image
Category: High voltage electrical appliances -- Indoor vacuum circuit breaker
Column tabs 
Price: factory price
Brand: 长城
Place of Origin: China
Column tabs 
Available Quantity: batch
delivery cycle: Spot goods (or inquire by telephone)
tabs
  Shanghai Beiyuan Industry and Trade Co.,Ltd
+86-21-66770508
+86-139101609058

Email 91way@163.com
Wechat 13916500500(Wechat)


CVS Sealed pole vacuum circuit breakerDetailed product description:Column tabs
1、 Significant features:
CVSl vacuum circuit breaker is equipped with CG68 spring mechanism or CG69 permanent magnet mechanism, which is an independent integral mechanism
Simple structure with few components,
Compact structure, small volume, and light weight;
Fully functional and highly reliable,
The distribution of operation buttons and status indicators is neat and centralized;
Easy maintenance:
During maintenance, the entire mechanism can be replaced and repaired,
Parts can also be replaced and repaired on the circuit breaker.

2、 The latest SIEMENS vacuum arc extinguishing chamber technology
Low cut-off value, low contact resistance,
High mechanical and electrical lifespan, with minimal contact wear during the lifespan
Longitudinal magnetic field contact

3、 Sealed main circuit
The vacuum arc extinguishing chamber is vertically sealed inside an insulating cylinder to prevent damage to the 1G vacuum extinguishing chamber caused by external factors
Flexible sealing materials can reduce the impact of circuit breaker operation vibration on vacuum arc extinguishing chambers
Effectively blocking the creepage on the surface of the vacuum extinguishing chamber, reducing its volume.

4、 Coordination between operating mechanism and vacuum arc extinguishing chamber
Using PRO-E kinetic analysis and calculation, verified through experiments. With this cooperation, the contact burns are minimal
Compact structural design
The circuit breaker has few components, a reasonable and compact structural layout, and the coordination between the operating mechanism and the vacuum arc extinguishing chamber

5、 CVS solid sealed pole vacuum circuit breaker has a wide range of applications
The circuit breaker can be applied to various mid mounted removable switchgear such as KVN28 and KYN79, and can also be fixedly installed.

6、 Range of CVS solid sealed pole vacuum circuit breaker

Rated maggot circuit breaking current

Rated short-circuit opening and closing current

rated current

12kV

12kV

(4000M)

24kV

25kA

63kA

630—1250A

CVSl

CVSl

CVSl

1600A

CVSl

CVSl

CVSl

1250A

CVSl

CVSl

CVSl

31.5kA

100kA

1600A

CVSl

CVSl

CVSl

2000A

CVSl

CVSl

CVSl

1250-2000A

CVSl

CVSl

CVSl

40kA

130kA

2500 to 3150A

CVSl

CVSl

CVSl

1600 to 2500A

CV51

CVSl

CVSl

50kA

130kA

1250 to 4000A

CVSl

CVSl

CVSl



7、 Selection table for bundled contacts

Rated current (A)

six hundred and thirty

one thousand two hundred and fifty

630-2000

1600 to 2000

2500—3150

1250-4000

Rated short-circuit breaking

Current (kA)

20—21

20—25

31.5

31.5—40

31.5—40

ten

Static contact diameter (mm)

Ø3

Ø49

Ø49

Ø79

Ø109

Ø109


8、 Technical data
Main technical parameters table of circuit breaker

serial number

Name

unit

Numerical value

l

rated voltage

kV

twelve

Rated Absolute

LMIN32 frequency withstand voltage

kV

forty-two

two

Edge level

Impulse withstand voltage (peak value)

seventy-five

three

rated current

A

six hundred and thirty

one thousand two hundred and fifty

one thousand and six hundred

two thousand

one thousand two hundred and fifty

two thousand

two thousand and five hundred

three thousand one hundred and fifty

four

Rated short-circuit breaking current

twenty-five

31.5

forty

five

Rated short-circuit closing current (peak)

eighty

80(100)

100(130)

six

Rated peak withstand current

kA

eighty

80(100)

100(130)

seven

Rated short-time withstand current

twenty-five

31.5

forty

eight

Electrical lifespan

time

thirty

nine

Rated short-circuit current duration

S

four

ten

Rated operating sequence

Split -0.3s - Split -180s - Split - Split

eleven

mechanical life

time

twenty thousand

twenty thousand

twenty thousand

twelve

Rated breaking current of a single capacitor bank

A

six hundred and thirty

thirteen

Rated back-to-back capacitor bank breaking current

A

four hundred


Note: In parentheses, to increase the closing current value, the user's special request is to provide
CVS1-12/T630-25,CVS1-12/T1250-31.5,CVS1-12/T1600-31.5
Mechanical characteristic parameter table

serial number

Name

unit

Numerical value

one

Contact opening distance

eight+0.5-1.5

two

Contact itinerary

mm

3.5±0.5

three

Center distance between phases

170±1.5  210±1.5

four

Bouncing time of closing contact

≤2

five

Three phase asynchronous disconnection

≤2

six

Opening time

highest

When the operating voltage is

rated

30-50

minimum

seven

closing time

ms

35-75

eight

Opening speed (just 5mm)

m/s

1.4±0.2

nine

Average opening speed (5mm before closing)

0.8±O.2


CVS1-12/T2000-31.5,CVS1-12/T1250-40,CVS1-12/T3150-40
Mechanical characteristic parameter table

serial number

Name

unit

Apply value

one

Contact opening distance

10±1

two

Contact itinerary

mm

3±O.1

three

Center distance between phases

275±1.5

four

Bouncing time of closing contact

≤2

five

Three phase asynchronous disconnection

≤2

highest

six

Opening time

When the operating voltage is

rated

30-65

minimum

seven

closing time

ms

35-75

eight

Opening speed (just 5mm)

m/s

1.4±0.2

nine

Average opening speed (5mm before closing)

0.8±0.2


energy storage motor

rated voltage

(V)

Huding input power

(W)

Normal operating voltage range

(V)

Energy storage time

(S)

DC220、DCll0

seventy-five

85% -110% rated voltage

≤15


*The operating voltage allows the use of AC and DC power sources.

Opening and closing coil

closing coil

trip coil

Rated operating voltage (Y)

AC220、DC220

ACll0、DCll0

AC220、DC220

ACll0、DCll0

Coil current (A)

one point four five

two point two

one point four five

two point two

Normal operating voltage range

85% to 110% rated voltage

65% to 120% rated voltage


CVS Sealed pole vacuum circuit breaker
Product Category
All product information on this website is translated by Baidu machine translation, which may not be completely accurate and is only for reference