| Product name: | CVS Sealed pole vacuum circuit breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Indoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | 长城 | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
Rated maggot circuit breaking current |
Rated short-circuit opening and closing current |
rated current |
12kV |
12kV (4000M) |
24kV |
|
25kA |
63kA |
630—1250A |
CVSl |
CVSl |
CVSl |
|
1600A |
CVSl |
CVSl |
CVSl | ||
|
1250A |
CVSl |
CVSl |
CVSl | ||
|
31.5kA |
100kA |
1600A |
CVSl |
CVSl |
CVSl |
|
2000A |
CVSl |
CVSl |
CVSl | ||
|
1250-2000A |
CVSl |
CVSl |
CVSl | ||
|
40kA |
130kA |
2500 to 3150A |
CVSl |
CVSl |
CVSl |
|
1600 to 2500A |
CV51 |
CVSl |
CVSl | ||
|
50kA |
130kA |
1250 to 4000A |
CVSl |
CVSl |
CVSl |
|
Rated current (A) |
six hundred and thirty |
one thousand two hundred and fifty |
630-2000 |
1600 to 2000 |
2500—3150 |
1250-4000 |
|
Rated short-circuit breaking Current (kA) |
20—21 |
20—25 |
31.5 |
31.5—40 |
31.5—40 |
ten |
|
Static contact diameter (mm) |
Ø3 |
Ø49 |
Ø49 |
Ø79 |
Ø109 |
Ø109 |
|
serial number |
Name |
unit |
Numerical value | ||||||||
|
l |
rated voltage |
kV |
twelve | ||||||||
|
Rated Absolute |
LMIN32 frequency withstand voltage |
kV |
forty-two | ||||||||
|
two |
Edge level |
Impulse withstand voltage (peak value) |
seventy-five | ||||||||
|
three |
rated current |
A |
six hundred and thirty |
one thousand two hundred and fifty |
one thousand and six hundred |
two thousand |
one thousand two hundred and fifty — two thousand |
two thousand and five hundred — three thousand one hundred and fifty | |||
|
four |
Rated short-circuit breaking current |
twenty-five |
31.5 |
forty | |||||||
|
five |
Rated short-circuit closing current (peak) |
eighty |
80(100) |
100(130) | |||||||
|
six |
Rated peak withstand current |
kA |
eighty |
80(100) |
100(130) | ||||||
|
seven |
Rated short-time withstand current |
twenty-five |
31.5 |
forty | |||||||
|
eight |
Electrical lifespan |
time |
thirty | ||||||||
|
nine |
Rated short-circuit current duration |
S |
four | ||||||||
|
ten |
Rated operating sequence |
Split -0.3s - Split -180s - Split - Split | |||||||||
|
eleven |
mechanical life |
time |
twenty thousand |
twenty thousand |
twenty thousand | ||||||
|
twelve |
Rated breaking current of a single capacitor bank |
A |
six hundred and thirty | ||||||||
|
thirteen |
Rated back-to-back capacitor bank breaking current |
A |
four hundred | ||||||||
|
serial number |
Name |
unit |
Numerical value | |
|
one |
Contact opening distance |
eight+0.5-1.5 | ||
|
two |
Contact itinerary |
mm |
3.5±0.5 | |
|
three |
Center distance between phases |
170±1.5 210±1.5 | ||
|
four |
Bouncing time of closing contact |
≤2 | ||
|
five |
Three phase asynchronous disconnection |
≤2 | ||
|
six |
Opening time |
highest |
||
|
When the operating voltage is |
rated |
30-50 | ||
|
minimum | ||||
|
seven |
closing time |
ms |
35-75 | |
|
eight |
Opening speed (just 5mm) |
m/s |
1.4±0.2 | |
|
nine |
Average opening speed (5mm before closing) |
0.8±O.2 | ||
|
serial number |
Name |
unit |
Apply value | |
|
one |
Contact opening distance |
10±1 | ||
|
two |
Contact itinerary |
mm |
3±O.1 | |
|
three |
Center distance between phases |
275±1.5 | ||
|
four |
Bouncing time of closing contact |
≤2 | ||
|
five |
Three phase asynchronous disconnection |
≤2 | ||
|
highest |
||||
|
six |
Opening time When the operating voltage is |
rated |
30-65 | |
|
minimum | ||||
|
seven |
closing time |
ms |
35-75 | |
|
eight |
Opening speed (just 5mm) |
m/s |
1.4±0.2 | |
|
nine |
Average opening speed (5mm before closing) |
0.8±0.2 | ||
|
rated voltage (V) |
Huding input power (W) |
Normal operating voltage range (V) |
Energy storage time (S) |
|
DC220、DCll0 |
seventy-five |
85% -110% rated voltage |
≤15 |
|
closing coil |
trip coil | |||
|
Rated operating voltage (Y) |
AC220、DC220 |
ACll0、DCll0 |
AC220、DC220 |
ACll0、DCll0 |
|
Coil current (A) |
one point four five |
two point two |
one point four five |
two point two |
|
Normal operating voltage range |
85% to 110% rated voltage |