The ZN23-40.5C series vehicle mounted high-voltage vacuum circuit breaker (hereinafter referred to as the circuit breaker) is an indoor high-voltage electrical equipment with a rated voltage of 40.5kV and three-phase AC 50Hz. It is suitable for power transmission and distribution systems in industrial and mining enterprises, substations, etc., and serves as a control and protection switch; Especially suitable for industries such as metallurgy and arc steelmaking that require frequent operations, as control and protection equipment.
The ZN23-40.5C series car type indoor high-voltage vacuum circuit breaker meets the standard of G1984-89 "AC Vacuum Circuit Breaker".
This circuit breaker is a handcart type, with a reasonable structure, easy maintenance, and safe and reliable use. Equipped with CD10 Ⅱ electromagnetic actuator or CT19 Ⅱ spring actuator.
2. Normal usage conditions
a) Altitude: not exceeding 1000m;
b) Surrounding air temperature: upper limit+40 ℃, lower limit -15 ℃;
c) Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%;
d) Water vapor pressure: daily average not exceeding 2.2kPa, monthly average not exceeding 1.8kPa;
e) The surrounding air is not significantly polluted by dust, smoke, corrosive and flammable gases, vapors, and salt spray;
f) Places without severe vibrations;
g) Any requirements beyond the above conditions shall be agreed upon by the user and the manufacturing unit.
3. Main technical parameters of ZN23-40.5C series car type indoor high-voltage vacuum circuit breaker:
| serial number |
name |
unit |
data |
| one |
rated voltage |
kV |
forty point five |
| two |
Lightning impulse withstand voltage (peak value) |
one hundred and eighty-five |
| three |
1-minute power frequency withstand voltage |
ninety-five |
| four |
rated frequency |
Hz |
fifty |
| five |
rated current |
A |
six hundred |
| six |
Rated short-circuit breaking current |
kA |
twenty-five |
| seven |
Rated short-circuit withstand current of 4s |
twenty-five |
| eight |
Rated peak withstand current |
eighty |
| nine |
Rated short-circuit breaking time |
ms |
≈90 |
| ten |
Rated short-circuit closing current (peak) |
kA |
eighty |
| eleven |
Rated operating sequence |
|
0-0.3s-CO-180s-0 |
| twelve |
closing time |
ms |
50~85 |
| thirteen |
Opening time |
40~85 |
| fourteen |
Rated short-circuit breaking current breaking times |
time |
twenty |
| fifteen |
mechanical life |
twelve thousand |
| sixteen |
Rated breaking current of capacitor bank |
A |
six hundred and thirty |
| seventeen |
Rated power of energy storage motor |
W |
two hundred and seventy-five |
| eighteen |
Rated voltage of energy storage motor |
V |
≈ 220, 110 |
| nineteen |
Energy storage time |
s |
fifteen |
| twenty |
Rated voltage of closing and opening electromagnet |
V |
≈ 220, 110 |
| twenty-one |
Rated voltage for voltage loss trip |
≈ 220, 110 |
| twenty-two |
Rated current for overcurrent trip |
A |
five |
| twenty-three |
Rated current of auxiliary switch |
ten |

ZN23-40.5C series car type indoor high-voltage vacuum circuit breaker