ZW8P-12/630-20 outdoor prepaid metering vacuum circuit breaker is a three-phase AC 50Hz, rated voltage 12kV outdoor vacuum circuit breaker and metering integrated switchgear. It is matched with a three-phase multifunctional meter to realize the opening and closing of load current, overload current, and short-circuit current in the distribution system, and has a high-precision high-voltage metering device, realizing active energy meter, reactive energy meter, active demand meter, power factor meter, prepaid meter, recording, and automatic meter reading. Using international standard IC card RS485 interface, infrared communication, large screen LCD display technology, flexible preset of multiple functions, and IC card or handheld computer as a medium to achieve information transmission between users and power supply department computers. The power department can choose one or more transmission methods based on local conditions to facilitate computer network management and meet the needs of modern and scientific management for users in an effective and timely manner.
ZW8P-12/630-20 outdoor prepaid metering vacuum circuit breaker model and its meaning:

Usage environment:
1. Altitude: not exceeding 1000 meters (exceeding is considered high altitude).
2. Surrounding air temperature: -45 ℃ to+40 ℃
3. Relative temperature: daily average not exceeding 95%, monthly average not exceeding 790%.
4. Wind speed: not exceeding 35m/s.
5. No flammable, explosive, chemical corrosion, or severe vibration hazards.
Main technical parameters of ZW8P-12/630-20 outdoor prepaid metering vacuum circuit breaker
|
Project
|
unit
|
numerical value
|
|
rated voltage |
KV |
twelve |
|
Rated insulation level
|
1min power frequency withstand voltage
|
Dry test |
KV
|
forty-two |
|
Wet test (ground test) |
thirty-four |
|
Lightning impulse withstand voltage (peak value) |
seventy-five |
|
rated current |
A |
six hundred and thirty |
|
rated frequency |
Hz |
fifty |
|
Rated short-circuit breaking current |
KA
|
16. 20 |
|
Rated short-circuit closing current (peak) |
40, 50 |
|
Rated peak withstand current |
40, 50 |
|
Rated short-circuit withstand current 4s |
16. 20 |
|
operating sequence |
Min-0.3s HeFen-180s HeFen |
|
Rated short-circuit current breaking times |
time |
thirty |
|
mechanical life |
time |
ten thousand |
|
Secondary circuit 1min power frequency withstand voltage |
kV |
two |
|
Rated current of overcurrent release device |
A |
five |
The external dimensions and installation dimensions of ZW8-12/630-20 outdoor prepaid metering vacuum circuit breaker:

The external dimensions and installation dimensions of ZW8-12/630-20 outdoor combination transformer:

Ordering Notice:
1. Product model, name, rated voltage, current, breaking capacity, and protection against CT changes.
2. Combination transformer box current transformer variation, precision level, voltage transformer ratio, accuracy, whether capacity is required, three column and five column.
3. Technical requirements for control circuits.
4. Whether to configure external connection cables, specifications, models, and quantities.
5. Order quantity and accessories.
6. Equipped with manual or electric operating mechanisms, with optional operating voltages of AC110V, AC220V, DC110V, and DC220V; If the customer requests not to bring a combination transformer, in principle, the customer should provide their own operating power supply. The customer has a special request for the supplier to provide an operating power supply, which can be equipped with a built-in voltage transformer for supply.
7. Measurement CT and PT require dry built-in, and should be ordered according to special negotiation.