VS1-40.5 indoor high-voltage vacuum circuit breaker is mainly used in three-phase AC 50Hz power systems with a rated voltage of 40.5kV. It can be used for protection and control in industrial and mining enterprises, power plants, and substations, especially suitable for various frequent operating places. This product complies with the requirements of GB11022 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards", GB1984 "AC High Voltage Circuit Breakers", IEC56 "High Voltage AC Circuit Breakers" and other standards.
Main technical parameters of VS1-40.5 indoor high-voltage vacuum circuit breaker (indoor high-voltage vacuum circuit breaker VS-40.5 type)
| serial number |
project |
unit |
Technical Specifications |
| one |
Contact opening distance |
mm |
18~20 |
| two |
overstroke |
3~5 |
| three |
Allowable wear thickness of contacts |
three |
| four |
Average opening speed (8mm after contact separation) |
m/s |
1.0~1.5 |
| five |
Average closing speed (12mm before contact closure) |
0.5~0.9 |
| six |
Contact closing bounce time |
≤3 |
| seven |
Three phase asynchronous disconnection |
≤2 |
| eight |
Three phase closing asynchrony |
ms |
≤2 |
| nine |
closing time |
≤90 |
| ten |
Opening time |
≤60 |
| eleven |
DC resistance of each phase conductive circuit (between the upper and lower plum blossom contacts) |
μΩ |
1250A |
1600A,2000A |
| ≤50 |
≤40 |
| twelve |
Interphase center distance |
mm |
300±2 |
| serial number |
project |
unit |
Technical Specifications |
| one |
rated voltage |
kV |
forty point five |
| two |
Rated insulation level |
1-minute power frequency withstand voltage |
ninety-five |
| Lightning impulse withstand voltage (peak value) |
one hundred and eighty-five |
| three |
rated current |
A |
630,1250,1600,2000 |
| four |
Rated short-circuit breaking current |
kA |
twenty |
twenty-five |
thirty-one point five |
| five |
Rated short-circuit closing current (peak) |
fifty |
sixty-three |
eighty |
| six |
Rated operating sequence |
|
0-0.3s-Co-180s-Co |
| seven |
Rated out of step breaking current |
kA |
five |
six point two five |
eight |
| eight |
Rated out of phase short circuit opening and closing |
seventeen point four |
twenty-one point seven |
twenty-seven point four |
| nine |
Average DC component of rated short-circuit breaking current |
|
≤48% |
| ten |
Rated breaking current of capacitor bank |
A |
four hundred |
| eleven |
Rated short-circuit duration |
S |
four |
| twelve |
Rated short-circuit breaking current breaking times |
time |
twenty |
| thirteen |
Cut off time |
ms |
≤80 |
| fourteen |
mechanical life |
time |
twenty thousand |
| fifteen |
Circuit breaker quality |
Kg |
two hundred and sixty |
VS1-40.5 Indoor High Voltage Vacuum Circuit Breaker Appearance and Installation Dimensions (Indoor High Voltage Vacuum Circuit Breaker VS-40.5 Type)