Scope of application:
The ZW7 series circuit breaker is suitable for use in three-phase AC 50Hz, 40.5kV power systems as a means of breaking and closing load currents, overload currents, and short-circuit currents. It can be used for the control and protection of power equipment and power lines in power plants and substations, as well as in places with frequent operations. It is an ideal product for the upgrading and replacement of the oil-free transformation of the 40.5kV old substation.
ZW7-40.5 series outdoor high-voltage vacuum circuit breaker model:

ZW7-40.5 outdoor high-voltage vacuum circuit breaker (hereinafter referred to as the circuit breaker) is used in three-phase power systems with AC 50Hz and voltage of 40.5kv, for breaking and closing load current, overload current, and short-circuit current.
a、 Adopting vacuum arc extinguishing, with strong breaking ability, long electrical life, and mechanical life of 10000 times:
b、 Simple structure, maintenance free, long maintenance free cycle;
c、 Good insulation performance and strong anti pollution ability;
d、 Can be equipped with spring or electromagnetic operating mechanism, reliable mechanical performance, and can be operated frequently; No fire and explosion hazards;
e、 The internal current transformer has a measurement accuracy of 0.2 level and can achieve three-phase differential protection;
f、 Equipped with a leakage controller, it can protect the circuit breaker from reliable operation under certain temperature and humidity conditions.
a. Surrounding air temperature: upper limit+40 ℃, lower limit -30 ℃ (general areas), -40 ℃ (high-altitude areas);
b. Altitude: ≤ 1000m (if altitude needs to be increased, the rated insulation level should be correspondingly raised);
c. Wind pressure: not exceeding 700pa (equivalent to a wind speed of 34m/s);
d. Amplitude: The seismic intensity does not exceed 8 degrees;
e. Pollution level: Level III;
f. Maximum daily temperature difference; Not exceeding 25 ℃
3、 Main technical parameters of ZW7-40.5 series outdoor high-voltage vacuum circuit breaker
| serial number |
name |
unit |
data |
| one |
rated voltage |
KV |
forty point five |
| two |
Rated insulation level |
1-minute power frequency withstand voltage |
Dry test |
ninety-five |
| wet test |
eighty |
| Lightning impulse withstand voltage (peak value) |
one hundred and eighty-five |
| three |
rated current |
A |
1250; 1600; two thousand |
| four |
Rated short-circuit breaking current |
KA |
20;25; thirty-one point five |
| five |
Rated operating sequence |
|
Min-0.3s HeFen-180s HeFen |
| six |
Rated short-circuit breaking current times |
time |
twelve |
| seven |
Rated short-circuit closing current (peak) |
KA |
50;63; eighty |
| eight |
Rated peak withstand voltage |
| nine |
Rated short-time withstand current |
20;25; thirty-one point five |
| ten |
Rated short-circuit duration |
S |
four |
| eleven |
Average opening speed |
M/S |
1.5±0.2 |
| twelve |
Average closing speed |
0.7±0.2 |
| thirteen |
Contact closing bounce time |
MS |
≤2 |
| fourteen |
Three phase closing (opening) synchronization time difference |
≤2 |
| fifteen |
closing time |
≤150 |
| sixteen |
Opening time |
≤60 |
| seventeen |
mechanical life |
time |
ten thousand |
| eighteen |
Rated operating voltage and rated voltage of auxiliary circuit |
V |
DC 110/220 |
| AC 110/220 |
| nineteen |
Direct resistance of each static circuit (excluding transformers) |
μΩ |
≤100 |
| twenty |
Allowable wear thickness of dynamic and static contacts |
MM |
three |
| twenty-one |
weight |
KG |
eight hundred |


ZW7-40.5 series outdoor high-voltage vacuum circuit breaker