main purpose
1、 ZW6-12/630 outdoor high-voltage vacuum circuit breaker is suitable for use in three-phase AC 50HZ, rated 12KV power grids. It is used for dividing and closing load currents, overload currents, and closing and breaking currents, and can also be used as a section switch for 12KV urban or rural power grids.
2、 This product operates in a reclosing state and, when equipped with a suitable control system, can be used as a recloser or segmenter in power lines.
3、 It can be independently applied to small and medium-sized substations, with the characteristics of reducing land occupation and saving investment.
4、 Whether used in power lines or in substations, there are smart units that can be equipped with grid automation and PW to achieve local and remote control.
Usage environment
1、 Surrounding air temperature: upper limit of 40 ℃, lower limit of -40 ℃;
2、 Altitude ≤ 2000m;
3、 Wind pressure: not exceeding 700pa (equivalent to a wind speed of 34m/s);
4、 The earthquake intensity shall not exceed magnitude 8.
Technical parameters of ZW6-12 outdoor high-voltage vacuum circuit breaker
| moon |
Technical parameter name |
unit |
Technical Specifications |
| 16KA |
20KA |
| one |
rated voltage |
KV |
twelve |
| two |
rated current |
A |
six hundred and thirty |
| three |
1-minute power frequency withstand voltage |
Dry test |
KV |
forty-two |
| Warm test |
KV |
thirty |
| four |
Lightning impulse withstand voltage (peak value) |
KV |
seventy-five |
| five |
Rated short-circuit breaking current |
KA |
sixteen |
twenty |
| six |
Rated short-circuit closing current (peak) |
KA |
forty |
fifty |
| seven |
Rated peak withstand voltage |
KA |
forty |
fifty |
| eight |
4S short-time withstand voltage |
KA |
sixteen |
twenty |
| nine |
Rated operating sequence |
|
Split -0.3s Split -180S Split - Split |
| ten |
Rated short-circuit current rise and break times |
time |
thirty |
| eleven |
mechanical life |
time |
ten thousand |
| twelve |
Rated voltage of energy storage motor |
V |
AC/DC 110.220 |
| thirteen |
Rated operating voltage |
trip coil |
V |
AC/DC 110.220 |
| closing coil |
| fourteen |
Allowable wear thickness of dynamic and static contacts |
mm |
three |
| fifteen |
Contact opening distance |
mm |
9±1 |
| sixteen |
Contact overtravel |
mm |
3±1 |
3±1 |
| seventeen |
Average closing speed |
m/s |
0.6±0.2 |
| eighteen |
Average opening speed |
m/s |
1.0±0.2 |
1.1±0.2 |
| nineteen |
Bounce time of Heku |
ms |
≤2 |
| twenty |
Three phase disconnection at different stages |
ms |
≤2 |
≤2 |
| twenty-one |
Opening time (equipped with CT type spring operating mechanism) |
s |
≤0.1 |
| twenty-two |
Closing time (equipped with CT type spring operating mechanism) |
Maximum operating voltage |
s |
≤0.06 |
| Minimum operating voltage |
≤0.1 |
| twenty-three |
DC resistance of each phase circuit |
UΩ |
≤200 |
| twenty-four |
Center distance between phases |
mm |
one hundred and ninety-three |
ZW6-12 Outdoor High Voltage Vacuum Circuit Breaker Outline and Installation Dimensional Drawing

ZW6-12 Outdoor High Voltage Vacuum Circuit Breaker