| Product name: | ZW43-12 Outdoor AC High Voltage Vacuum Circuit Breaker | ||||||
| specification: | ![]() |
||||||
| Category: | High voltage electrical appliances -- Outdoor vacuum circuit breaker | ||||||
| Price: | factory price | ||||||
| Brand: | Shanghai | ||||||
| Place of Origin: | China | ||||||
| Available Quantity: | batch | ||||||
| delivery cycle: | Spot goods (or inquire by telephone) | ||||||
|
|||||||
|
serial number |
project |
unit |
parameter |
|
one |
rated voltage |
KV |
twelve |
|
two |
rated frequency |
Hz |
fifty |
|
three |
rated current |
A |
six hundred and thirty |
|
four |
Rated short-circuit breaking current |
KA |
twenty |
|
five |
Rated peak withstand current (peak) |
KA |
fifty |
|
six |
Rated short-term durability current |
KA |
twenty |
|
seven |
Rated short-circuit closing current (peak) |
KA |
fifty |
|
eight |
mechanical life |
time |
ten thousand |
|
nine |
Rated short-circuit breaking current breaking times |
time |
thirty |
|
ten |
Power frequency withstand voltage (1min): (wet) (dry) phase to phase, ground/fracture |
KV |
30/42/48 |
|
eleven |
Lightning impulse withstand current (peak value) phase to phase, ground/fracture |
KV |
75/85 |
|
twelve |
Secondary circuit 1-minute power frequency withstand voltage |
KV |
two |
|
serial number |
project |
unit |
parameter |
|
one |
Contact opening distance |
mm |
9±1 |
|
two |
Contact overtravel |
mm |
2±0.5 |
|
three |
Opening speed |
m/s |
1.0±0.2 |
|
four |
closing speed |
m/s |
0.6±0.2 |
|
five |
Contact closing bounce time |
ms |
≤2 |
|
six |
Center distance between phases |
mm |
340±1.5 |
|
seven |
Three phase opening and closing asynchrony |
ms |
≤2 |
|
eight |
Resistance of each phase conductive circuit |
μΩ |
<80 |
|
nine |
closing time |
ms |
25~45 |
|
ten |
Opening time |
ms |
23~45 |